Cable’s Rated Voltage and Range of use
Cables in accordance with IEC 60502-1 are intended for fixed installation :
• indoors
• outdoors
• underground
• in water
(Note: The relevant national installation regulations must be observed) Nominal and highest cable voltages
|
Nominal rated voltage U0/U |
Highest system voltage U0 |
||
kV |
Three phase system (kV) |
Single phase system (kV) |
Single phase system (kV) |
|
Low voltage (LV) acc to IEC 60502-1 |
0.6 / 1 |
1.2 |
1.4 |
0.7 |
1.8 / 3 |
3.6 |
4.2 |
2.1 |
|
Medium voltage (MV) acc to IEC 60502-2 |
3.6 / 6 |
7.2 |
8.3 |
4.2 |
6 / 10 |
12.0 |
14.0 |
7.0 |
|
8.7 / 15 |
17.5 |
20.0 |
10.0 |
|
12 / 20 |
24.0 |
28.0 |
14.0 |
|
18 / 30 |
36.0 |
42.0 |
21.0 |
1) both phases insulated
2) one phase grounded
3) max.voltage in d.c. systems 1.8 kv
U : Rated power-frequency voltage between phase conductors for which the cable is suitable.
U0 : Rated power-frequency voltage between conductor and earth or armour, metal sheath or screen for which the cable is suitabel.
Um : Maximum value of the “highest system voltage” between phase conductors for which the cable is suitable.
|
IEC Ratings |
BSI Equivalent |
U0 /U (Um) kV |
1.8 / 3 (3.6) * |
1.9 / 3.3 (3.6) * |
3.3 / 6 (7.2) |
3.8 / 6.6 (7.2) |
|
6 / 10 (12) |
6.35 / 11 (12) |
|
8.7 / 15 (17.5) |
8.7 / 15 (17.5) |
|
12 / 20 (24) |
12.7 / 22 (24) |
|
18 / 30 (36) |
19 / 33 (36) |
* 1.8 kV cable is referred to IEC 60502-1 and BSI 5467